Scope Of Work

At the request of DPR Construction Inc., Genelco performed an extensive series of testing and commissioning services at the Digital Realty Trust Data Center in California. The project started with conference calls, site visits and drawing and submittal reviews. This full-site testing and commissioning effort focused on all of the critical and essential electrical and mechanical systems which supported the data center facility.

Custom step-by-step procedures were produced, reviewed and utilized during these tests. Digital Realty Trust is the world's largest host of rented data center space and due to the complexity of the site configuration, several infrared reports were created. An Issues and Resolutions Log was also created, starting with day one of the overall testing and commissioning process.
?
With regard to actual procedures performed, the UPS modules and the generators were subjected to incremental loading, four hour 100% load burn-ins, followed by large step loading, UPS battery discharge tests (also referred to as battery run down tests), were performed on each of the individual UPS modules and each PDU was exercised through a burn-in cycle per the included procedures. Additionally, the mechanical systems, (chillers, pumps, CRAH’s, AHU’s, and other associated hardware and control systems) were commissioned and responded appropriately to numerous full and partial utility failure scenarios.

After the individual components were proven, Genelco conducted a multi-scenario system wide Integrated test or "pull the plug" test.

Over the course of the project, components and systems commissioned included:
(3) 750 kW UPS modules with battery
(1) 2000AMP UPS system control cab
(1) 2000 kW generator
(6) 125 & 225 kVA PDU
(3) 1600, 2000 and 1000A automatic transfer switches
(53) 100 amp and larger circuit breakers
(3) Critical distribution panels
(2) 230 ton cooling towers
(4) 30 ton CRAC units for computer room
(3) 20 ton CRAC units for UPS room
(2) XD coolant chillers for high density area
(1) Leak detection system
(1) Exhaust fans for battery room
(1) Pre-action system/ FM 200 system
(1) Fire alarm system
(1) BMS system & EPO system
(1) Ground system witness testing
(2) 5 ton water source heat pumps
(1) Projector(s) exhaust system
(2) 7.5 ton water source heat pumps
(1) 100KVA UPS module