Featured Project Return to Projects List
Chilled Water system Heat Exchanger Replacement
Project Information
- Project Location:
- City of Industry, CA
- Status:
- Completed - Oct 2019
- Structure Type:
- Manufacturing Plant
Scope Of Work
Chilled Water System heat exchanger replacement:
Failed plate type heat exchanger introduced water to the Chiller Refrigeration system. Removed defective plate heat exchanger, flushed refrigeration circuit with nitrogen to removed water from the Refrigeration system, installed new shell and tube heat exchanger, refrigerant pipes and chilled water pipes piping, installed new suction line filter dryer, replaced liquid line filter dryers, add new oil to the Compressor, leak test, refrigeration system vacuum, system charged with refrigerant and start up