Company Info

  • Est. 1994
  • Annual Vol Undisclosed

Featured Project Return to Projects List

Chilled Water system Heat Exchanger Replacement

Project Information

Project Location:
City of Industry, CA
Status:
Completed - Oct 2019
Structure Type:
Manufacturing Plant

Scope Of Work

Chilled Water System heat exchanger replacement:

Failed plate type heat exchanger introduced water to the Chiller Refrigeration system. Removed defective plate heat exchanger, flushed refrigeration circuit with nitrogen to removed water from the Refrigeration system, installed new shell and tube heat exchanger, refrigerant pipes and chilled water pipes piping, installed new suction line filter dryer, replaced liquid line filter dryers, add new oil to the Compressor, leak test, refrigeration system vacuum, system charged with refrigerant and start up